Description
Product function
- Split core type structure, which can be installed without changing cables
- High-quality epoxy resin vacuum casting, excellent mechanical and environmental resistance
- High-quality stainless steel clamp hoop fastening structure, easy and reliable installation
- Output terminal type, more concise wiring
- Single winding protection current transformer
TECHNICAL PARAMETERS
Dimensions (D×d×H) | 153mm×105mm×83mm | |
Rated frequency | 50Hz | |
Rated secondary current | 5A | |
Rated burden | ≤2.5VA | |
Applicable cable outer diameter | ≤φ94mm | |
Rated primary current range | 100A | |
Dielectric strength | AC3000V,1min | |
Rated continuous overcurrent | 120% of rated current | |
Polarity and homonym | P2 represents the primary polarity terminal,
S1, S2 represent the secondary polarity end, P2 and S2 have the same polarity (-polarity) at the same instant |
|
Working environment | Temperature | -25℃~40℃ |
Humidity | ≤90% | |
Altitude | ≤1000m |
TECHNICAL DATA
Model | LXZK1 | ||||
Accuracy class & Rated burden(VA) | Accuracy class & Rated burden(VA) | ||||
Type | Current transformer for protection | Current transformer for measurement | |||
Current rating PRI:SEC Amperes |
5P10 | 10P10 | 0.5 | 1.0 | 3 |
20/1 | 1 | √ | |||
50/1 | 1 | 1.5 | √ | √ | |
75/1 | 1.5 | 2.5 | √ | √ | |
100/1 | 2.5 | 3.75 | √ | √ | |
150/1 | 2.5 | 5 | √ | √ | √ |
50/5 | 1 | √ | |||
75/5 | 1 | 1.5 | √ | √ | |
100/5 | 1.5 | 2.5 | √ | √ | |
150/5 | 2.5 | 3.75 | √ | √ |
ORDERING INFORMATION